Optimal Placement of a Resistive Superconducting
Fault Current Limiter in a Multimachine Power
System
Journal:
GRENZE International Journal of Engineering and Technology
Authors:
Asha Alex, Muhamed Noufal C
Volume:
3
Issue:
2Special Issue
Grenze ID:
01.GIJET.3.2Special Issue
Pages:
175-180
Abstract
This paper presents a method to find the optimal position of resistive
superconducting fault current limiter (SFCL) for transient stability enhancement of multimachine
power system. The method is based on minimization of rotor angle separation of
synchronous machines present in the system. The SFCL can have different impacts (positive
and negative) according to its resistance value and location in the power system when a fault
occurs. The studies are carried out on the loop electrical power system based on the
Western System Coordinated Council (WSCC) three machines, nine-bus system to evaluate
the effectiveness of the method by using MATLAB. The optimal location of SFCL combine
with its resistive valve reduces the angular separation of the rotors that improve effectively
the system stability during fault.